Climate Doctor
Your Prescriptions for Comfort
 
P.O. Box 661
Payson, UT 84651
(801) 426-6367
 
 Repair Service  AL | Climate Doctor

Cooling Equipment Efficiency Criteria

Air-Source Heat Pumps and Central Air Conditioner
Key Product Criteria

Equipment Specification
Air-Source Heat Pumps >= 8.2 HSPF/ >=14 SEER/ >=11.5 EER* for split systems
>= 8.0 HSPF/ >=14 SEER/ >=11 EER* for single package equipment including gas/electric package units
Central Air Conditioners >=14 SEER/ >=11.5 EER* for split systems
>=14 SEER/ >=11 EER* for single package equipment including gas/electric package units

*Energy Efficiency Ratio

Air-Source Heat Pump (ASHP):

An air-source unitary heat pump model consists of one or more factory-made assemblies which normally include an indoor conditioning coil(s), compressor(s), and outdoor coil(s), including means to provide a heating function. ASHPs shall provide the function of air heating with controlled temperature, and may include the functions of air-cooling, air-circulation, air-cleaning, dehumidifying or humidifying.

Central Air Conditioner:

A central air conditioner model consists of one or more factory-made assemblies which normally include an evaporator or cooling coil(s), compressor(s), and condenser(s). Central air conditioners provide the function of air-cooling and may include the functions of air-circulation, air-cleaning, dehumidifying or humidifying.

Heating Seasonal Performance Factor (HSPF):

This is a measure of a heat pump's energy efficiency over one heating season. It represents the total heating output of a heat pump (including supplementary electric heat) during the normal heating season (in Btu) as compared to the total electricity consumed (in watt-hours) during the same period. HSPF is based on tests performed in accordance with ARI 210/2401.

Seasonal Energy Efficiency Ratio (SEER):

This is a measure of equipment energy efficiency over the cooling season. It represents the total cooling of a central air conditioner or heat pump (in Btu) during the normal cooling season as compared to the total electric energy input (in watt-hours) consumed during the same period. SEER is based on tests performed in accordance with ARI 210/2401.

Energy Efficiency Ratio (EER):

This is a measure of the instantaneous energy efficiency of cooling equipment. EER is the steady-state rate of heat energy removal (e.g., cooling capacity) by the equipment in Btuh divided by the steady-state rate of energy input to the equipment in watts. This ratio is expressed in Btuh per watt (Btuh/watt). EER is based on tests performed in accordance with ARI 210/2401.

1Air-Conditioning and Refrigeration Institute. Standard 210/240 "2003 Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment."


Energy Star - U.S. Environmental Protection Agency - U.S. Department of Energy